RCTA Air Conditioning
|
| RCTA-B036 "A" Coils are shipped with all "6" Pistons (57, 60, 65, 67, 71 and 73), one bottom adaptor frame, two horizontal support brackets and new coil tubing and drain panel for HQA and coil boxes. |
RCTA Replacement coils carry a 1 (one) Year WarrantyOr the balance of the warranty period of a listed coil
|
Coils may not be suited for all original applicationsThe information provided below is a summary from the RCTA-B036 "A" coil Installation Instructions. It is intended to provide information that might be helpful in determining if this replacement coil is the right choice for a particular application. Installation Instructions and parts are shipped with each replacement "A" coil. The index page will take you to the original coil specification sheet for any questions you might have about original coils. RCTA Index. See the Installation Instructions for more details regarding the information shown below. |
| IMPORTANT INFORMATION BELOW REGARDING THE USE OF THE RCTA-B036 "A" COIL HAS NOT BEEN TESTED AND WE CANNOT ASSURE PROPER PERFORMANCE IN HEAT PUMP APPLICATIONS |
|---|
REFRIGERANT CHARGING: Charging by Super Heat (Cool Mode charging only for Heat Pumps; check operation in Heating Mode, below 50 degrees) |
TXV Coil Replacements: The RCTA-B036 coil is a piston coil. In some cases the original coil will have a TXV. |
HORIZONTAL APPLICATIONS : Horizontal applications limited to RXCH-A14 drain pans
which limit HORIZONTAL applications to RHQA-12 and -13 Air Handlers. |
DOWNFLOW APPLICATIONS :Most application. however, the RCTA-B style coil in Downflow applications is limited to airflow ranges below 1050 CFM |
DOWNFLOW WARNING :THE RCTA-B036 IN NOT RECOMMENDED IN THE DOWNFLOW POSITION WHEN AIRFLOW EXCEEDS 1050 CFM (2.5 Tons) |
UPFLOW/DOWNFLOW: RCTA-B036 can be used for application in RXAL-B16, 20 and 22 original coil boxes, with modification and /or parts shipped with the coil. |
RHQA air-handlers: RHQA models may require modification using parts sent
with the coil, or removal of parts from the air-handler. |
Heat Pumps: This coil is intended for Air Conditioner applications only. If you have a heat pump application please contact your local Rheem or Ruud distributor for assistance. |