RPWL
Charging Information
Basic System Charge is for 0 feet of
refrigerant line.
Use the table below to determine how much refrigerant is needed per foot
of refrigerant line.
| Required ounces of R-410A charge per foot of tubing. |
Tube Size O.D. (IN.) [mm] |
Liquid Line (OZ.) [g] |
Vapor Line (OZ.) [g] |
| 1/2 [12.7] |
1.06 [30.0] |
.04 [1.13] |
| 5/8 [15.89] |
1.65 [46.7] |
.07 [1.98] |
| 3/4 [19.05] |
2.46 [69.7] |
.10 [2.83] |
| 7/8 [22.23] |
3.28 [92.9] |
.13 [3.68] |
| 1-1/8 [28.58] |
-- |
.22 [6.23] |
| 1-3/8 [34.93] |
-- |
.34 [9.63] |
| 1-5/8 [41.28] |
-- |
.48 [13.60] |
| 2-1/8 [53.98] |
-- |
.84 [23.81] |
|