Tech Tips
Low Suction Pressure/Normal Superheat
TXV Systems
FI0021
- Low Airflow
- undersized duct, return and/or supply
- improperly installed duct, return and/or supply
- dirty air filter
- air filter with excessive resistance to air flow
- closed or blocked supply or return registers
- more than one filter installed
- bad blower motor and/or capacitor
- incorrect blower motor
- blower wheel not turning proper direction
- loose blower belt
- incorrect sheave adjustment
- incorrect drive package for application
Note: If air handlers are the (-)BHA, (-)BEA, (-)BHB, (-)BHJ, (-)BEH series, consult the installation instructions for specific duct connection requirements.
- Low Load
- low return air temperature
- dirty or matted indoor coil
- recirculation of supply air into return air
- Unit Overcharge
- Bad Indoor Blower Motor and/or Motor Capacitor
- Incorrect Blower Motor, Motor Capacitor, or Blower Wheel
- Unit Operating in Low Ambient Conditions
|