T117_A - Detect RPM Motor Failure

EcoNet - A117_A ยป

Status

Motor RPM failure is not a critical fault per say. However, the furnace will lose constant airflow functionality.

Description

The RPM signal from the motor has not been detected for more than 20 seconds while the motor is being commanded to run.

Expected Operation

If the RPM signal is not detected and the fault becomes active, the control shall run the blower in constant torque mode instead of constant airflow mode. In such a case, the airflow from the registers may feel more or less than normal.

Cause

There could be multiple reasons causing this failure:

1. Broken RPM cable between the motor and the air handler control.

2. Bad blower motor.

3. Broken PWM cable between the air handler control and the motor.

4. Bad air handler control board.

5. No power to the blower motor control module.

6. No line voltage to the blower motor.

Solution

A Technician should:

1. Check that wire assembly between fan and air handler controller is properly connected.

2. Inspect wiring for failed or broken wires or connectors, replace and/or repair as necessary.

3. If problem persists, replace air handler control or blower motor.