A924_O: Inverter Fault - Board Temp

EcoNet - A924_O ยป

Status

This is a critical alarm, the unit will remain off until the board temperature recovers

Description

Thermistors built into the drive board are measuring critical temperatures and must shut the unit down to protect the drive.

Expected Operation

No operation.

Cause

Low resistance values to compressor or path to ground. Check windings for open or shorted conditions. Verify heat sink on back of drive is clean.

Solution

1. Check compressor and fan motor winding resistance. Make sure no windings are shorted or open.

2. If compressor and fan motor windings are within tolerance, replace inverter drive controller.