T957_O: Low Refrigerant Pressure

EcoNet - T957_O ยป

Description

The UUODC controller has detected low refrigerant pressure for the operating conditions.

Expected Operation

If the event occurs within the same call 3 times, the system will switch from an Alert to an Alarm and lock the unit out for 4 hours.

Cause

1. Too little refrigerant in the system.

2. Leak or under-charging.

Solution

Check refrigerant charge - compare pressure readings to published values for the unit at the current ambient temp. Adjust refrigerant charge level as necessary.