A315_S Indoor Unit Refrigerant Detected Sensor 1

EcoNet - A315_S ยป

Status

This is a critical fault. A2L sensing device is faulty.

Description

This fault is set if the A2L refrigerant sensor has an internal fault.

Expected Operation

If an A2L refrigerant sensor has an internal fault and is able to communicate it to the furnace, the control declares this alarm. Cooling, heat-pump heating, and defrost operation is inhibited until the alarm condition goes away. Gas heating maybe permitted. Circulating blower airflow will be as appropriate for an A2L refrigerant leak event. If the sensor fault goes away, alarm will be cleared and control will resume normal operation after a 5 minute delay.

Cause

Faulty A2L refrigerant leak detection sensor.

Solution

Replace A2L refrigerant leak detection sensor.