Portal econet_a111f

A111_F: One-Hour Lockout: Main Limit/HALC Switch

EcoNet - A111_F »

Status

This is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function. 

Description

Alarm "A022_F Main Limit/HALC Switch Open" and "A111_F One-hour Lockout: Main Limit/HALC Switch" is logged if the main limit/HALC trips for longer than 150 seconds four times in a single heat call.

Expected Operation

The limit circuit is monitored during gas heating (including defrost) and post-purge. If the main limit/HALC trips, control logs "T022_F Main Limit/HALC Switch Open", shuts off the inducer and gas valves, and runs the blower at the highest heat speed.

If the limit remains tripped for more than 150 seconds, alert “T022_F Main Limit/HALC Switch Open” is elevated to an alarm "A022_F Main Limit/HALC Switch Open". Blower will run at the highest heat speed. Alarm “A061_F Blower Fault - Motor Cannot Run” is also logged at this point. Upon reclosing of the limit, the control will clear alarm "A022_F Main Limit/HALC Switch Open" and transition to blower off delay without any need for inducer to go through post-purge. The control then enters a 1-hour soft lockout. Alarms "A111_F One-hour Lockout: Main Limit/HALC Switch" and "A061_F Blower Fault - Motor Cannot Run" are declared throughout the duration of the lockout. After the lockout period expires, both alarms are cleared and normal operation resumes.

Cause

1. No airflow

2. Insufficient airflow

3. Faulty Limit Control

4. Loose or Faulty Wiring

5. Dead (non-functional) blower

6. Input too high

Solution

1. Check for proper blower operation. Is the blower turning during heat (or any other) mode? If not, a blower motor fault may also be present. Check the wiring to the motor then check the motor. It may need replacing.

2. Check duct work and filters. Determine the static pressure and make sure it is not above the published values for the furnace. Check the rate and outlet air temperature for high and low heat using a jumper wire between R and W/W1 respectively. Compare them to the nameplate maximum values and adjust if necessary. If a supply air sensor is used cycle power to the furnace.

3. Replace the faulty limit control.

4. Check wiring and connections. Replace and/or repair as necessary.

5. Insure properly sized burner orifices are installed. Check the manifold pressure at high fire and compare to the nameplate values. Adjust as needed.

6. Input too high, adjust as needed.