Portal econet_a20charging

(-)A20 Inverter Condenser

What can I help you find?

Charging

Charging a system at commissioning or after a repair is one thing. Walking up to a unit and slapping gauges on is a different story. You must remember, above all, the charging chart is to be used for charging. You cant put your gauges on, and look at pressures when you don't know what speed the compressor is running, what airflow is being delivered, or if the load is what it needs to be. Read on...

Are you looking for the charging chart?

(-)A2024 Charging Chart »

(-)A2036 Charging Chart »

(-)A2048 Charging Chart »

(-)A2060 Charging Chart »

Factory Charge Values

Size Weight
(-)A2024 148 Ounces
(-)A2036 193.6 Ounces
(-)A2048 196 Ounces
(-)A2060 376 Ounces

Charging Process

Charging an inverter system requires a skill level above that of an entry level service technician, but is otherwise pretty straight forward. You surely noticed these are not 8 or 10 SEER units with pistons or capillary tube metering devices, so we can’t treat them as such. The details are crucial to achieve proper charge. First and foremost a technician needs to understand is that there must be a specific load on the coil in order for pressures to line up with the ones on the chart. We’ve all seen in the past, on a high load, the suction is higher than it is on a low load, right? In other words, an 80 degree home will have a higher suction pressure than it would if it were 70 in the house, no?

So how do we ensure we have a load similar to that used in the development of the charging charts? It is safe to say, we don’t have control over the outdoor temperature, so the charts are made to accommodate various outdoor temps. We do however have the ability to control the indoor temperatures. After all that’s what we do for a living.

Airflow, or the quantity of air that carries heat, is also crucial to achieve a proper charge. This may mean turning off any airflow adjustments and de-humidification to provide design airflow. You can turn all that back on after you have completed the charging task at hand. None of those were in play when the charts were developed for the sake of consistency.

Finally, since these are variable speed units, it is important to have the compressor running at the designated speed. For the (-)P17, (-)A20 or (-)P20A Models, this speed is high speed. Below, we will provide that speed by model number.

The following criteria must be achieved in order for charging to work.

• For Charging in Cooling, the Outdoor Temperature must be between 55 and 99 degrees.

• Indoor temperature must be 80 degrees F +/- 2 degrees.

• For Charging in Heating, the Outdoor Temperature must be between 40 and 60 degrees F.

• Indoor temperature must be 70 degrees F +/-2 degrees

• The system must be matched

• The coils and filters must be clean

• Airflow Adjustments and De-humidification must be turned off.

• Compressor must be running at high speed

o (-)A2024 – 3000 RPM for Cool

o (-)A2036 – 4680 RPM for Cool

o (-)A2048 – 3800 RPM for Cool

o (-)A2060 – 4800 RPM for Cool

• Verify Airflow is where it needs to be for the equipment.

o 2 Ton – 800 CFM

o 3 ton – 1200 CFM

o 4 ton – 1500 CFM

o 5 ton – 1700 CFM

If the system has been wired legacy or an RH2T air handler is being used, you will need to verify airflow in a traditional manner. This does not lessen the importance even though it’s more work.

When applied with an EcoNet thermostat (601 series, rev 42 or later, or 700 series). You may go to the menu and find the service icon, and select OD checkout. You may set the variable speed test to high cool, or high heat depending on the mode you are going to charge it in. You may still access the status screens. Once the compressor RPM’s are at high, verify airflow.

Allow the system to operate on the factory charge for a while. I would love to say 15 minutes, and while that may be the case occasionally, it won’t hurt to go 30 or 40 minutes before attempting to adjust the charge.

Measure the outdoor temperature (the temperature of the air going into the outdoor coil) and plot this on the charging chart. It’s important to remember all the key bullets listed above. It needs to be 80 degrees, plus or minus 2 degrees entering the indoor coil. If the head pressure is lower than the chart add refrigerant. If it’s higher, remove some refrigerant. Wait for a period of 15 minutes before making additional adjustments. Once you have pressures similar to those on the chart, allow the system to stabilize and then you can look at the subcooling. Do NOT go straight to subcooling.

Subcooling is used to overcome a pressure drop in the liquid line. The smaller or longer the line, the more pressure drop the subcooling must overcome. If you have a short line set, chances are you can be a little short on subcooling and be just fine. Overcharges can cause failures related to high discharge pressures such as envelope faults, overcurrent and others. Do NOT overcharge the system. The old adage of “If a little is good, a lot is better” does not, and never has applied to refrigeration.

IF you are commissioning the system in temperatures below 40 degrees or above 99 degrees, you will most certainly have to get it close and plan a return trip to finalize the charge when conditions are suitable. There is data in the charging chart for conditions outside of these ranges, but they are not going to be 100% correct, especially in heating below 40 because the accumulator may be storing some of the refrigerant and above 100 degrees, it’s too easy to overcharge the system.