T030_Z - Too Many Zones for Outdoor Unit Model

EcoNet - T030_Z ยป

Status

System will operate as a single zone, ignoring any zone controls

Description

(-)A15, (-)A16 and (-)P16 Mid Tier inverters are limited to two zones only. The Thermostat has found more than two zones and will not allow more than 2. This change is effective in (-)ETS800SYS firmware version AC-RHUI-03-02-04 and later.  Regardless of firmware version, mid tier inverters may only have 2 zones and may require a small bypass.

Expected Operation

System will operate in heating and cooling but will ignore zoning.

Cause

1. Too many zones

2. Address for second zone was changed to 3 or higher.

Solution

1. Remove additional zones.

2.Be sure zone 2, if only 2 zones are present is designated as zone 2.