T006_F: Horsepower Conflict on Memory Card

EcoNet - T006_F »

IFC - d1 »

Status

This is a non-critical fault. The furnace should operate in any mode.

Description

The horsepower reported by the motor does not match the horsepower stored in the model data. However, the hp of the motor does match the hp stored in the microprocessor on the furnace IFC.

Cause

There are two possible causes for this fault. 1. The blower motor has recently been replaced and the wrong horsepower motor was used. 2. The memory card has recently been replaced and the incorrect model data card was used.

Solution

Determine the correct motor or model data card and replace the incorrect part with the correct part. Do not borrow a model data card from another product, especially a condenser or air handler. A replacement motor or model data card can be ordered from your distributor. Make sure you have the complete model and serial number of the furnace when ordering parts.