A814_O Inverter- AC Input Sampling Fault

EcoNet - A814_O ยป

Status

No operation when Alarm is Present. Operation will resume if Alarm clears. After three strikes without 15 minutes of continuous operation, a permanent lockout (requiring power reset) will occur.

Description

Compressor drive has declared an internal fault and cannot detect the voltage sensor connected to the voltage input.

Expected Operation

Critical Fault - No operation until corrected.

Cause

Compressor drive cannot read the voltage to the input side.

Solution

  • Check and correct wiring and electrical connectors to drive and compressor.
  • Replace Compressor Drive.
  • Replace compressor.