T960_O or A960_O: Compressor Locked Rotor

EcoNet - A960_O »

OD - 4 or L04 »

On the outdoor unit control, this will be indicated by a number 4 or L4 on the seven segment LED display.

This alarm means that the compressor is pulling excessive current at start up. This could be from off cycle migration leaving the compressor full of refrigerant, it could also be a result of a weak capacitor or tight or seized compressor. Verify capacitor micro-farads, warm top of compressor shell to chase any liquid out.