T086_F - Suction Pressure Sensor Failure

EcoNet - T086_F ยป

Status

This is a critical fault for furnaces that use electronic expansion valve. Suction pressure is used in the algorithm that drives the electronic expansion valve.

Description

This fault indicates the suction pressure sensor is either open or shorted, or has been removed after being installed.

Expected Operation

The fault "T086_F Suction Pressure Sensor Failure" will be declared. Cooling operation will struggle due to this fault.

Cause

1. Suction pressure sensor was installed and removed without cycling power.

2. Suction pressure sensor or wiring has failed.

3. Bad furnace control board.

Solution

1. If no suction pressure sensor was ever installed, cycle power to remove fault and check control for indication of condensation that may have temporarily tricked it into thinking one had been installed.

2. Replace suction pressure sensor.

3. Replace furnace control board.