T082_F: Supply Air Sensor Fault

EcoNet - T082_F »

IFC - 82 »

Status

This is a non-critical fault. Supply air temperature is used only for display purposes on the EcoNet Thermostat.

Description

This fault indicates the accessory supply air sensor is either open or shorted.

Expected Operation

The fault will be displayed but the furnace will continue to operate.

Cause

1. Supply air sensor was installed and removed without cycling power.

2. Supply air sensor or wiring to it has failed.

Solution

1. If no supply air sensor was ever installed, cycle power to remove fault and check IFC for indication of condensation that may have temporarily tricked IFC into thinking one had been installed.

2. Replace Supply air sensor.