T947_O: Inverter Fault - DC Bus Undervoltage

EcoNet - T947_O ยป


Description

The DC Bus Voltage is too low

Expected Operation

Unit will shutdown until DC Bus voltage returns to normal. If this happens 3 times, unit will Lockout requiring a manual reset.

Cause

1. Incoming AC Voltage is lower than it should be.  DC Voltage is directly related to AC incoming voltage.

2. Defective Inverter Drive

Solution

1. Check input voltage to unit. Should be above 180VAC. If under this voltage, voltage must be corrected or fault will persist.

2. If the input voltage is above 180VAC and problem persists, replace inverter drive controller.