A816_O: Inverter- Fan 2 Fault

EcoNet - A816_O ยป

Status

No operation when Alarm is Present. Operation will resume if Alarm clears. After three strikes without 15 minutes of continuous operation, a permanent lockout (requiring power reset) will occur.

Description

The compressor drive has detected a fault with the #2 fan motor control circuit (4 & 5 ton systems only).

Expected Operation

Critical Fault - No operation until corrected.

Cause

Compressor drive has detected an error on the fan circuit (fan #2 only).

Solution

  • Check and correct wiring and electrical connectors to drive, compressor and fan
  • Replace Fan.
  • Replace compressor drive.