A031_F: Open Fuse

EcoNet - A031_F »

Status

This is a critical fault. The furnace will not operate in any mode.

Description

The fuse has been opened. This usually occurs when there is a 24VAC short to common or ground on the low voltage side of the transformer.

Expected Operation

A conductive fuse is always expected be present for normal operation. If however, the fuse is sensed open, the IFC will:

  1. Ignore all requests. Possible operation in progress finishes in the same way as if the request was removed.
  2. Alarm “A031_F Open Fuse” is declared.
  3. During the time the fuse is sensed open, treats the rollout limit switch, main limit switch, heat assisted limit control and both auxiliary inputs as closed to assure correct reaction on the open fuse condition (otherwise the switches would be falsely sensed open).

Once the fuse is sensed conductive again, the IFC shall revert back to normal operation and the alarm will be cleared.

Cause

An electrical short from low voltage (24VAC) to ground or common has occurred.

Solution

Repair the short circuit condition and replace fuse.