T085_A - Evap Temp Thermistor Failure
Status
This is a passive alarm, the air handler will operate normally with this alarm.
Solution
Technician should make sure control board is dry and cycle power to system to see if fault clears.
Determine cause of moisture building or accumulating on control board such as low airflow, or blow off from coil.
If problem persists, replace Air Handler control.