A010_F: One-Hour Lockout

EcoNet - A010_F »

IFC - 10 »

Status

This is a critical fault, the furnace will not operate in gas heat mode, although other modes of operation such as cooling or fan only modes will.

You will have to check the fault history to see which alert converted to an alarm. For Example after four T011_F Failed ignition attempts, it will convert to an A010_F lockout alarm.

Description

The fault is displayed under the following conditions

1. When a failed ignition has occurred 4 times in a row, the control enters the one-hour lockout and fault codes "10" and "11" will be displayed alternately at the seven-segment display. See fault code 11 (T011_F) for a description, causes and a solution for this fault.

2. After declaring a water sense condition and shutting the furnace down several times consecutively. When the control enters the one-hour lockout, fault codes "10" and "59" will be displayed alternately. See fault code 59 (T059_F) for a description, cause and solution.

3. If the furnace has declared a dead blower because the main limit opened and did not reset within 150 seconds. The fault code "10" and "61" will be displayed alternately on the seven segment display. See fault code 61 (A061_F).

4. When an IFC fault "93" is active. The fault code "10" and "93" will be displayed alternately. See fault 93 (A093_F).

5. When flame is LOST 5 times in a row. The display will register "10" and "13" alternately. See fault 13 (T013_F).

6. While the furnace is in a one-hour lockout after experiencing an unexpected flame. "10" and "14" will be alternately displayed. See fault 14 (A014_F).