A071_F: Inducer Fault
Status
This is a critical fault. The furnace will not operate gas heat mode, but all other modes (e.g. cooling) should function if present simultaneously with a heating call (e.g. Defrost call in dual fuel mode).
Description
This fault indicates the inducer is not working properly. Note: This fault may be seen under normal operating conditions if power is lost and returned quickly (within 30 seconds) while operating in gas heat mode.
Expected Operation
The fault is displayed when too much or too little current is detected on the inducer circuit.
Cause
1. Power outage.
2. Bad wiring to the inducer.
3. Bad inducer.
4. Bad furnace control.
Solution
1. Reset power to unit and clear fault.
2. Check wiring and connections between IFC and Inducer. Correct/replace as necessary.
3. Replace inducer
4. Replace furnace control (IFC).