A956_O: Suction Pressure Sensor Failure

EcoNet - A956_O ยป

Status

System will not operate.

Description

The outdoor suction transducer is out of range or reading open or shorted. 

Expected Operation

System will shutdown and will restart when resolved

Cause

Moisture in transducer, Harness to transducer is not seated properly at either end or harness is defective.

Solution

Check transducer against calibrated gauges and replace if necessary. Inspect wiring harness for proper seating and visible damage and replace if necessary.