Status
The unit should continue to run in the cooling mode with this fault but it should not be left alone. Will negatively impact defrost on heat pumps as system will not know when coil is frosted or defrosted.
Description
The UODC control can no longer detect the temperature from the specified sensor.
Expected Operation
Minor operational changes using default value for operational calculations instead of measured values.
Solution
1. Verify sensor is properly connected to UODC and Check the thermistor against the 10k thermistor chart.
2. Replace sensor.
3. Replace Universal UODC controller.