A025_Z
Zoning Not Compatible With Air Handler
Status
This is a critical fault. The system will not operate as a EcoNet zoned system
Description
EcoNet zoning requires specific furnaces and air handlers. This fault is specific to the air handlers. It cannot be made to work.
Cause
Its pretty simple. The EcoNet zoning system is not designed to work with the RH2T air handler.
It was designed and must be paired with one of the models listed under the zoning tab.
Solution
Until the RH2T air handler is replaced with an RHMV, zoning will not be compatible with this system.
You may either remove the EcoNet zoning system and install an off the shelf, legacy wired zoning system such as can be provided by EWC.
OR
Replace the RH2T air handler with an RHMV air handler or appropriate gas furnace and coil.
There is NO WAY to make this system operate with the RH2T air handler so don't ask.