T022_F: Main Limit/HALC Switch Open

EcoNet - T022_F ยป

Status

This is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function. 

Description

Alert "T022_F Main Limit/HALC Switch Open" is logged if the main limit or heat-assisted limit control (HALC) trips.

Expected Operation

The limit circuit is monitored during gas heating (including defrost) and post-purge. If the main limit/HALC trips, control logs "T022_F Main Limit/HALC Switch Open", shuts off the inducer and gas valves, and runs the blower at the highest heat speed.

If the limit re-closes in less than 150 seconds, the control will clear alert "T022_F Main Limit/HALC Switch Open" and transition to blower off delay without any need for inducer to go through post-purge. If a call for heat remains after the off-delay is complete, the furnace will go into a normal ignition cycle. If the limit opens four times in one heat call, alert "T022_F Main Limit/HALC Switch Open" will be elevated to an alarm "A022_F Main Limit/HALC Switch Open".

Cause

1. No airflow

2. Insufficient airflow

3. Faulty Limit Control

4. Loose or Faulty Wiring

5. Dead (non-functional) blower

6. Input too high

Solution

1. Check for proper blower operation. Is the blower turning during heat (or any other) mode? If not, a blower motor fault may also be present. Check the wiring to the motor then check the motor. It may need replacing.

2. Check duct work and filters. Determine the static pressure and make sure it is not above the published values for the furnace. Check the rate and outlet air temperature for high and low heat using a jumper wire between R and W/W1 respectively. Compare them to the nameplate maximum values and adjust if necessary. If a supply air sensor is used cycle power to the furnace.

3. Replace the faulty limit control.

4. Check wiring and connections. Replace and/or repair as necessary.

5. Insure properly sized burner orifices are installed. Check the manifold pressure at high fire and compare to the nameplate values. Adjust as needed.

6. Input too high, adjust as needed.