T921_O: Inverter Fault - Comp. Overcurrent

EcoNet - T921_O ยป

Status

Unit will shut down and attempt to restart successfully 3 times before locking out.

Description

Compressor is pulling more current than expected.

Expected Operation

System will shut down and try 3 times before locking out.

Cause

1. Compressor has a damaged winding or a locked rotor.

2. Compressor drive failed.

Solution

1. Verify that the compressor wires are not grounded .

2. Check compressor winding resistance relative to ground to see if compressor windings are shorted. If shorted, replace compressor.

3. If compressor windings OK, replace compressor drive controller.