A028_S: Room Temp High, > 10 degrees from setting
Status
Unit will continue to operate as long as no other faults are present
Description
Set point is 10 degrees lower than actual space temp for more than 2 hours. This fault is more of an alter than an alarm but had to be coded as such so remote homeowner would get it. Only alarms are sent to the EcoNet app.
Cause
1. System undersized or not able to keep up.
2. May be that set point was changed drastically on a set back or returning from an away condition and it has not yet recovered.
3. Set point accidentally set to low
Solution
1. Check system performance and capacity,
2. Verify set backs are not the issue.
3. Verify set point was not accidentally set to low.