A111_O: Communication Lost with Indoor Unit

EcoNet - A111_O ยป

Status

This is a critical alarm, the unit will not operate in any mode.

Description

This code is displayed anytime there is no communication as expected between the indoor unit and outdoor unt.

Expected Operation

No operation

Cause

Possible miswiring or damaged wire between indoor unit and outdoor unit control boards.

Solution

Verify wiring end to end at E1-E1, E2-E2, R-R, C-C.  Check for damaged wire or poor connections in low voltage wiring at either end or somewhere between.

If the problem persists, Replace control board.