A112_O: Expected Econet IDU Not Connected

EcoNet - A112_O ยป

Status

This is a critical alarm, there will be no operation when alarm is present. This is only a valid alarm on hybrid inverters and RP18/RA18 units with Regal Beloit and Emerson equipment.

Description

This code is displayed anytime there is no model data at the furnace. The model data is electronically stored data that is used to define (among other things) blower operation. Without model data, the furnace cannot function.

Expected Operation

No operation, including the thermostat will be permitted without the model data. The model data defines the IBM (Indoor Blower Motor) speed-torque curve. Without this information, the IBM cannot operate.

Cause

Faulty control board - possibly incorrect Bluetooth/EcoNet set up

Solution

Replace control board.