T958_O or A958_O: High Refrigerant Pressure

EcoNet - T or A 958_O »

OD - 29 or L29 »

On the outdoor unit control, this will be indicated by a number 29 or L29 on the seven segment LED display.

This alarm means that the high pressure switch has opened as a result of high refrigerant pressure. Verify charge, check condition of outdoor coil, verify outdoor fan motor is running as it should. System will lock out if high pressure switch trips 3 times in an single cooling call.