A228_F: Internal Fault: Gas Vlv Rly 2 Stuck Open

EcoNet - A228_F ยป

Status

This is a critical fault and should rarely (if ever) be seen in the field.

Description

High gas valve relay on 2-stage is stuck open causing ignition failures.

Expected Operation

If the gas valve relay is energized for ignition trial and the internal sensing circuit detects that there is no voltage on the gas valve output and flame is not established after four ignition tries, the gas valve will be de-energized and inducer will run through post-purge. The control will enter a 1-hour lockout with alarm "A113_F One-hour Lockout: Ignition Failure" declared together with "A228_F Internal Fault: Gas Vlv 2 Rly Stuck Open".

After the lockout is complete, the furnace clears alarms "A113_F One-hour Lockout: Ignition Failure" and "A228_F Internal Fault: Gas Vlv 2 Rly Stuck Open". The control then resumes normal operation.

Cause

Faulty furnace control - relay stuck open.

Solution

Replace furnace control (IFC).