Portal econet_a116f_m1

A116_F: One Hour Lockout: Flame Presence Alarm

EcoNet - A116_F »

Status

This is an extremely critical fault and should rarely (if ever) be seen in the field.

Description

The fault indicates a flame was present when it should not be. Flame is seen to be present when the gas valve is supposed to be off.

Expected Operation

Flame sense is monitored at all times. If flame is somehow sensed for more than four seconds when it is not expected (including standby, cooling and continuous fan operation), the unit will respond as follows:

1. Gas valve and igniter are turned off (if not already turned off). 

2. Inducer is energized immediately at high speed (if not already at high speed).

3. Indoor blower is energized at the high heat speed unless there is another call also present – in which case the higher speed shall be used.

4. "A127_F Flame Present with Gas Valve Off - UL" and “A014_F Flame Present with Gas Valve Off” alarms are immediately logged.

These states will remain as described above until the undesired flame is gone.

Once the undesired flame is no longer present, the furnace clears the alarm "A014_F Flame Present with Gas Valve Off", completes the inducer post-purge and the user set heat blower off delay. Alarm "A127_F Flame Present with Gas Valve Off - UL" will remain set. The IFC then proceeds to a one-hour “soft” lockout with the alarm  "A116_F One-hour Lockout: Flame Presence Alarm" declared throughout the duration. Upon completion of the lockout, IFC will clear alarm "A116_F One-hour Lockout: Flame Presence Alarm". Alarm "A127_F Flame Present with Gas Valve Off - UL" remains logged until power is cycled or a clear alarms command is used to clear the fault. The IFC shall then resume normal operation.

Causes

1. Field mis-wiring of gas valve.

2. Faulty gas valve relay that is stuck or sticking.

3. Faulty furnace control that is sensing flame when no flame is present.

4. Flame sense wire is grounded.

Solution

1. Wire Properly.

2. Replace furnace control (IFC)

3. Flame sense wire should be properly connected to flame sense rod and should not be grounded.